|
Sprinklers in Elevator Machine Rooms and Hoistways
Background
VA practice provides total sprinkler protection for all new patient
buildings. Existing VA buildings are also routinely provided with total
sprinkler protection retroactively. NFPA Standard No. 13 addressees proper
installation of sprinklers including requirement for sprinklers in the pit
and in the machine room. There are no exceptions for new construction
elevator machine rooms.
ASME A17.1 Elevator Code, Rule 102.2(c) allows sprinklers for elevator
machine rooms and pits but requires that power be disconnected to the
elevators prior to sprinkler activation in machine rooms.
The reason for the power disconnect requirement is the concern that unsafe
operating conditions may occur if a sprinkler discharges wetting the
elevator machinery and controllers. This could potentially allow the
elevator to move with the doors open. In extreme cases the elevator could
crash into the top or bottom of the hoistway.
The NFPA Fire Alarm Code (NFPA 72) requires that the heat detectors used
for elevator shutdown be connected to the fire alarm control panel for
alarm only.
Discussion
Elevator fire protection must comply with NFPA 13, NFPA 70, NFPA 72, and
ANSI/ASME A17.1 or A17.3 as applicable.
Sprinklers will be provided for all new elevator machine rooms and pits
in accordance with NFPA Standard No. 13 when the building is required to
be totally sprinkler protected. Sprinklers at the top of noncombustible
hoistways of passenger elevators whose car enclosure meets the requirements
of ASME A17.1 shall be omitted. The sprinkler in the pit is required for
hydraulic elevators or if oil buffers are present and the hoistway is of
combustible construction.
All sprinklers in the elevator machine room and bottom of the hoistway
shall be fed from the building wet pipe sprinkler system. No sprinkler
risers shall be permitted inside any hoistway. Sprinkler branch lines
shall enter hoistways only where a sprinkler is required. Sprinklers shall
be standard type with 165 degree temperature rating. A guard shall be
provided around each sprinkler. Control valves to isolate the sprinklers
shall be provided in an accessible location outside any hoistway or machine
room. A separate water flow switch shall be provided to create a separate
sprinkler zone. A tamper switch shall be provided for each control valve.
Flow and tamper switches shall be connected to the building fire alarm
system. Heat detectors, 135 degrees rate compensation with a lower Response
Time Index (RTI) shall be provided in accordance with NFPA 72 within 24
inches of each sprinkler in the elevator machine room. No heat detector is
required for the pit sprinkler. The heat detectors shall be connected to
the fire alarm control panel. The fire alarm control panel shall send a
supervised signal to the elevator machine room. Power shall be removed
from each elevator controller by activating an independently controlled
shunt trip circuit breaker when the temperature in the machine room exceeds
the setting of the heat detector.
Equivalent Protection
On a case-by-case basis for some minor renovation or upgrade work, sprinklers
may be omitted from the elevator machine room, the top of the hoistway, and
the bottom of the hoistway when sprinklers are retroactively installed in
existing buildings as follows:
- Elevator hoistways and machine rooms must be of non-combustible
construction.
- A one-hour fire rated enclosure must be provided around the elevator
machine room. Unprotected openings in the floor may be provided for
mechanical, hoist and governor cables. Fire doors to the elevator machine
rooms shall be provided with signage prohibiting the door being blocked
open. Hoistways must also be enclosed in fire rated construction, the
rating dependent on other code requirements.
- No occupancy or storage shall be permitted in the elevator machine
rooms. Quarterly inspections shall be conducted and documented.
- Heat detectors as described above shall be provided in the elevator
machine rooms to perform the functions as noted above. Spacing of the
heat detectors shall be per NFPA 72.
- For existing fire alarm systems being modified to include elevator
shutdown, follow requirements for new systems if technically feasible.
Otherwise, the heat detectors shall be part of an independent shutdown
system.
- All other provisions of Rule 211 of ASME A17.1 shall be provided.
For additional information contact the Consulting Support Service
(183A), Bill Haupt @ 202-565-9371.
|